Modbus Driver

VOLTTRON’s modbus driver supports the Modbus over TCP/IP protocol only. For Modbus RTU support, see VOLTTRON’s Modbus-TK driver <Modbus-TK-Driver>.

About Modbus protocol

Modbus Driver Configuration

Requirements

The Modbus driver requires the pymodbus package. This package can be installed in an activated environment with:

pip install pymodbus

Alternatively this requirement can be installed using bootstrap.py with the --drivers option:

python3 bootstrap.py --drivers

Driver Configuration

There are three arguments for the driver_config section of the device configuration file:

  • device_address - IP Address of the device.

  • port - Port the device is listening on. Defaults to 502 which is the standard port for Modbus devices.

  • slave_id - Slave ID of the device. Defaults to 0. Use 0 for no slave.

The remaining values are as follows:

Here is an example device configuration file:

{
    "driver_config": {"device_address": "10.1.1.2",
                      "port": 502,
                      "slave_id": 5},
    "driver_type": "modbus",
    "registry_config":"config://registry_configs/hvac.csv",
    "interval": 60,
    "timezone": "UTC",
    "heart_beat_point": "heartbeat"
}

A sample MODBUS configuration file can be found in the VOLTTRON repository in examples/configurations/drivers/modbus.config

Modbus Registry Configuration File

The registry configuration file is a CSV file. Each row configures a point on the device.

The following columns are required for each row:

  • Volttron Point Name - The name by which the platform and agents running on the platform will refer to this point. For instance, if the Volttron Point Name is HeatCall1 (and using the example device configuration above) then an agent would use pnnl/isb2/hvac1/HeatCall1 to refer to the point when using the RPC interface of the actuator agent.

  • Units - Used for meta data when creating point information on the historian.

  • Modbus Register - A string representing how to interpret the data register and how to read it from the device. The string takes two forms:

    • “BOOL” for coils and discrete inputs.

    • A format string for the Python struct module. See the Python3 Struct docs for full documentation. The supplied format string must only represent one value. See the documentation of your device to determine how to interpret the registers. Some Examples:

      • “>f” - A big endian 32-bit floating point number.

      • “<H” - A little endian 16-bit unsigned integer.

      • “>l” - A big endian 32-bit integer.

  • Writable - Either TRUE or FALSE. Determines if the point can be written to. Only points labeled TRUE can be written to through the ActuatorAgent.

  • Point Address - Modbus address of the point. Cannot include any offset value, it must be the exact value of the address.

  • Mixed Endian - (Optional) Either TRUE or FALSE. For mixed endian values. This will reverse the order of the Modbus registers that make up this point before parsing the value or writing it out to the device. Has no effect on bit values.

The following column is optional:

  • Default Value - The default value for the point. When the point is reverted by an agent it will change back to this value. If this value is missing it will revert to the last known value not set by an agent.

Any additional columns will be ignored. It is common practice to include a Point Name or Reference Point Name to include the device documentation’s name for the point and Notes and Unit Details for additional information about a point.

The following is an example of a Modbus registry configuration file:

Catalyst 371

Reference Point Name

Volttron Point Name

Units

Units Details

Modbus Register

Writable

Point Address

Default Value

Notes

CO2Sensor

ReturnAirCO2

PPM

0.00-2000.00

>f

FALSE

1001

CO2 Reading 0.00-2000.0 ppm

CO2Stpt

ReturnAirCO2Stpt

PPM

1000.00 (default)

>f

TRUE

1011

1000

Setpoint to enable demand control ventilation

Cool1Spd

CoolSupplyFanSpeed1

%

0.00 to 100.00 (75 default)

>f

TRUE

1005

75

Fan speed on cool 1 call

Cool2Spd

CoolSupplyFanSpeed2

%

0.00 to 100.00 (90 default)

>f

TRUE

1007

90

Fan speed on Cool2 Call

Damper

DamperSignal

%

0.00 - 100.00

>f

FALSE

1023

Output to the economizer damper

DaTemp

DischargeAirTemperature

F

(-)39.99 to 248.00

>f

FALSE

1009

Discharge air reading

ESMEconMin

ESMDamperMinPosition

%

0.00 to 100.00 (5 default)

>f

TRUE

1013

5

Minimum damper position during the energy savings mode

FanPower

SupplyFanPower

kW

0.00 to 100.00

>f

FALSE

1015

Fan power from drive

FanSpeed

SupplyFanSpeed

%

0.00 to 100.00

>f

FALSE

1003

Fan speed from drive

HeatCall1

HeatCall1

On / Off

on/off

BOOL

FALSE

1113

Status indicator of heating stage 1 need

HeartBeat

heartbeat

On / Off

on/off

BOOL

FALSE

1114

Status indicator of heating stage 2 need

A sample Modbus registry file can be found here or in the VOLTTRON repository in examples/configurations/drivers/catalyst371.csv